Rotronic Clean-Room Panel CRP1

products-servicesRotronic AG
August 22nd 2016

 

Overview

Rotronic’s CRP1 Clean-Room Panel is the obvious choice wherever small variances in pressure, temperature and humidity need to be constantly monitored in ultra hygienic environments such as laboratory clean rooms, hospital operating theatres, and in the pharmaceutical, electronics, and foodstuffs industries. It is GMP compliant and features compatibility with a wide range of sensors and remote probe calibration.

Applications

The CRP1 is designed for compact construction, easy wall mounting and simple handling. It incorporates distinctive technology and design to enable easier measurement and management of ultra-clean controlled environments.

The CRP1 features Rotronic HygroClip2-compatibility, allowing humidity to be registered to highest degrees of accuracy. Other Rotronic probes can be connected, depending on demand and application. CRP1 can display measured values, alarms and measurement curves. It can also transfer data via analog outputs or MODBUS.

Features

  • Monitors humidity, temperature and low dew point
  • Designed specifically for clean rooms
  • Works in combination with HygroClip2-series probes, with other Rotronic probes connectible (customized to specific application
  • FDA- and GAMP-compatible
  • Digital communication via MODBUS RTU / HW4
  • Analog output signals freely configurable
  • Stainless steel front panel highly resistant to chemicals for easy cleaning
  • Alarm output acoustic, or via relay or LCD display
  • Simple probe calibration remotely from outside room being monitored

Benefits

The well thought-out design makes the CRP1 perfect for applications in laboratories and clean rooms. The unit’s comprehensive functional capabilities provide solutions for many measurement and control tasks.

It can simultaneously monitor numerous variables, including differential pressure, humidity, and temperature.

The removable sensor and single glass surface, together with optical buttons, permit easier and more efficient cleaning and operation.

The new panel’s graphical color display can display up to six measurement values and messages and allows display colors to be individually set and changed. The unit can be configured directly using the panel buttons or remotely via RS 485 or Ethernet interface with PC or via MODBUS.

The display highlights alarms for faults, exceeded limit values, warnings, etc. Alerts can also be forwarded digitally via MODBUS, Ethernet, or relays. A mix of analog and digital communication capabilities makes the CRP1 very easy to integrate in any monitoring system.

CRP1 Specifications

Parameters Relative humidity and temperature
Dimensions 182 x 136 x 40 mm
Operating Range 750 g (without humidity probe)
Weight -10…60 °C / 0…100 %rh
Measurement Ranges -100…200 °C (probe-dependent) / 0…100 %RH
Accuracy Analog Output ±5 mV (voltage output), ±20 μA (current output)
Switch Output 2 Relays
Switching Capacity < 30 VDC at 2 A, < 50 VAC at 0.5 A
Power Supply / Power Consumption 10…36 VDC, <1 A
Electrical Connections Screw terminals on back
Display Type Illuminated graphic LCD
Menu Navigation 6 buttons
Analog Outputs 2, freely configurable
Analog Output Signal (Standard) 4…20 mA or 0…10 V
Permissible Load >10 kΩ (voltage output), <500 Ω (Current Output)
Communication Interfaces RS-485 (Modbus RTU, HW4)
Service Interface UART
Housing Stainless steel 1.4401, plastic (cleaning resistant)
Ip Protection Rating IP65 (built in)
Fire Protection Class Complies UL94-HB
Mounting Position Wall Mounting
FDA / GAMP compliance FDA 21 CFR part 11 / GAMP5
CE / EMC Compliance 2004/108/EC

 

Resources

Click on Rotronic Clean-Room Panel CRP1 for more information.
Click on Rotronic to contact the company directly.
Click on Products for more information on Rotronic measurement solutions.

CRP1 panel displaying showing relative humidity, ambient temperature and differential pressure readings

CRP1 panel displaying showing relative humidity, ambient temperature and differential pressure readings

CRP1 clean room panel features easy clean stainless steel fascia and easy wall mounting

CRP1 clean room panel features easy clean stainless steel fascia and easy wall mounting


Supplier Information
Supplier: Rotronic AG
Address: Grindelstrasse 6, CH-8303 Bassersdorf, Switzerland
Tel: +41 44 838 1144
Fax: +41 44 838 1487
Website: http://www.rotronic.com/